15/01/2007 1:32 AM

workshop wiring

This is a multi-part message in MIME format.

------=_NextPart_000_01F1_01C73845.12D02C00
Content-Type: text/plain;
charset="iso-8859-1"
Content-Transfer-Encoding: quoted-printable

I recently built a new detached shop (the kind of shop that my wife =
parks her van in). The electric service to the shop is fed from the =
house via 240V 50A breaker. When I had the electrical inspected, the =
inspector noted that since I had more than one circuit in the shop =
subpanel, the subpanel needed its own ground rod. The electrian came =
back and put the ground rod in and connected the wire from the ground =
rod to the neutral bus. The inspector came back again and said that the =
wire from the ground rod needed to be connected to the panel case =
instead of the neutral. I figured I could take care of that quickly =
myself, but now I have a question. There is a ground from the main =
panel that currently connects to the panel case. Do I leave that in =
place when I connect the wire from the new ground rod? In case a pic =
would help, here it is before I moved the new ground wire off the =
neutral bus.

http://www.freeimagehosting.net/uploads/0d19e399c3.jpg
The bottom left conduit is the service from the house with two hots, a =
neutral, and the ground wire. The conduit to the right of that is the =
wire that connects to the ground rod (the wire is black, but is marked =
as ground with green tape). I moved this wire to the ground connection =
in the bottom middle of the box, but I don't know what to do with the =
ground wire that is there now that connects back to the main panel.

todd

------=_NextPart_000_01F1_01C73845.12D02C00
Content-Type: text/html;
charset="iso-8859-1"
Content-Transfer-Encoding: quoted-printable

<!DOCTYPE HTML PUBLIC "-//W3C//DTD HTML 4.0 Transitional//EN">
<HTML><HEAD>
<META http-equiv=3DContent-Type content=3D"text/html; =
charset=3Diso-8859-1">
<META content=3D"MSHTML 6.00.5346.5" name=3DGENERATOR>
<STYLE></STYLE>
</HEAD>
<BODY>
<DIV><FONT face=3DArial size=3D2>I recently built a new detached shop =
(the kind of=20
shop that my wife parks her van in).&nbsp; The electric service to the =
shop is=20
fed from the house via 240V 50A breaker.&nbsp; When I had the electrical =

inspected, the inspector noted that since I had more than one circuit in =
the=20
shop subpanel, the subpanel needed its own ground rod.&nbsp; The =
electrian came=20
back and put the ground rod in and connected the wire from the ground =
rod to the=20
neutral bus.&nbsp; The inspector came back again and said that the wire =
from the=20
ground rod needed to be connected to the panel case instead of the=20
neutral.&nbsp; I figured I could take care of that quickly myself, but =
now I=20
have a question.&nbsp; There is a ground from the main panel that =
currently=20
connects to the panel case.&nbsp; Do I leave that in place when I =
connect the=20
wire from the new ground rod?&nbsp; In case a pic would help, here it is =
before=20
I moved the new ground wire off the neutral bus.</FONT></DIV>
<DIV>&nbsp;</DIV>
<DIV><A =
href=3D"http://www.freeimagehosting.net/uploads/0d19e399c3.jpg"><FONT=20
face=3DArial=20
size=3D2>http://www.freeimagehosting.net/uploads/0d19e399c3.jpg</FONT></A=
></DIV>
<P><FONT face=3DArial size=3D2>The bottom left conduit is the service =
from the house=20
with two hots, a neutral, and the ground wire.&nbsp; The conduit to the =
right of=20
that is the wire that connects to the ground rod (the wire is black, but =
is=20
marked as ground with green tape).&nbsp; I moved this wire to the ground =

connection in the bottom middle of the box, but I don't know what to do =
with the=20
ground wire that is there now that connects back to the main =
panel.</FONT></P>
<P><FONT face=3DArial size=3D2>todd</FONT></P></BODY></HTML>

------=_NextPart_000_01F1_01C73845.12D02C00--


This topic has 3 replies

Cc

"Charley"

in reply to "todd" on 15/01/2007 1:32 AM

15/01/2007 2:01 PM

This is a multi-part message in MIME format.

------=_NextPart_000_0011_01C738AD.B7B8FCC0
Content-Type: text/plain;
charset="iso-8859-1"
Content-Transfer-Encoding: quoted-printable

By code the Neutral is only permitted to be connected to ground at one =
point and that one point should be in the main electrical service panel. =

Now the code reuuires that the sub panel cabinet be connected to ground =
via the ground wire from the main panel and also via a #6 or larger =
copper wire to the ground rod. It wouldn't hurt to also connect a #6 =
ground wire from the panel ground to a clamp on any nearby metal water =
pipe, if one exists. Telephone, cable TV, and other electrical services =
should also be ground connected together, at least at one point on the =
property.

Before the code required that a sub panel in an out building had to be =
grounded via a separate ground rod, a 60' pine tree next to my shop was =
struck by lightning (3' away). It was such a large strike that the top =
16' of this pine tree was blown off and fell to the ground. The =
lightning also jumped from the tree trunk into the metal face of the =
door and then up from the top corners of the door through the 1/2" =
plywood sofitting above the door into the armored electrical cabling =
above the door (blew 1"X6" slots through the plywood). Although the =
electrical panel in the shop was grounded via the service cable from the =
shop to the main panel in the house, at the time I didn't have a =
separate ground rod installed at the shop, as it wasn't required by =
code. The ground connection via the electrical cable to the house =
aparently wasn't sufficient to carry the lightning load because the =
lightning jumped between the ground and neutral in the sub panel in the =
shop and went back to the main panel in the house that way too. This =
resulted in a large burn mark in the sub panel and burns between neutral =
and ground in many of the electrical outlet boxes both inside the shop =
and the house.=20

Four days later, while I was just sitting in the shop looking at some =
plans on my workbench, the receptacle directly behind my radial arm saw =
suddenly threw sparks and set fire to the wall around it. Nothing =
electrical in the shop was running at the time, except for the overhead =
lights, which are on a separate circuit. It's a good thing that I was =
there. I was able to quickly shut off the power and use an extinguisher =
to put out the fire on/in the wall. If I hadn't been sitting there when =
this happened I would have lost my whole shop.

After this incident I replaced many of the outlets in my shop and in my =
house, personally inspected all of them, and added a ground rod to my =
shop panel wiring. I now frequently take the time (at least once every =
spring) to check to be sure that my phone wiring, my cable TV wiring, =
and my house electrical panels are all ground connected to each other =
and to the ground rods. When I make this check I remove, clean, and =
replace any connection that appears not to be perfect.

I have always had a significant respect for lightning, but this incident =
enhanced this respect significantly.

--=20
Charley

"todd" <[email protected]> wrote in message =
news:[email protected]...
I recently built a new detached shop (the kind of shop that my wife =
parks her van in). The electric service to the shop is fed from the =
house via 240V 50A breaker. When I had the electrical inspected, the =
inspector noted that since I had more than one circuit in the shop =
subpanel, the subpanel needed its own ground rod. The electrian came =
back and put the ground rod in and connected the wire from the ground =
rod to the neutral bus. The inspector came back again and said that the =
wire from the ground rod needed to be connected to the panel case =
instead of the neutral. I figured I could take care of that quickly =
myself, but now I have a question. There is a ground from the main =
panel that currently connects to the panel case. Do I leave that in =
place when I connect the wire from the new ground rod? In case a pic =
would help, here it is before I moved the new ground wire off the =
neutral bus.

http://www.freeimagehosting.net/uploads/0d19e399c3.jpg
The bottom left conduit is the service from the house with two hots, a =
neutral, and the ground wire. The conduit to the right of that is the =
wire that connects to the ground rod (the wire is black, but is marked =
as ground with green tape). I moved this wire to the ground connection =
in the bottom middle of the box, but I don't know what to do with the =
ground wire that is there now that connects back to the main panel.

todd

------=_NextPart_000_0011_01C738AD.B7B8FCC0
Content-Type: text/html;
charset="iso-8859-1"
Content-Transfer-Encoding: quoted-printable

<!DOCTYPE HTML PUBLIC "-//W3C//DTD HTML 4.0 Transitional//EN">
<HTML><HEAD>
<META http-equiv=3DContent-Type content=3D"text/html; =
charset=3Diso-8859-1">
<META content=3D"MSHTML 6.00.2800.1476" name=3DGENERATOR>
<STYLE></STYLE>
</HEAD>
<BODY bgColor=3D#ffffff>
<DIV><FONT face=3DArial size=3D2>By code the Neutral is only permitted =
to be=20
connected to ground at one point and that one point should be in the =
main=20
electrical service panel. </FONT></DIV>
<DIV><FONT face=3DArial size=3D2>Now the code reuuires that the&nbsp;sub =
panel=20
cabinet&nbsp;be connected to ground via the ground wire from the main =
panel and=20
also via&nbsp;a #6 or larger copper&nbsp;wire to the ground rod. It =
wouldn't=20
hurt to also connect a #6 ground wire from the panel ground to a clamp =
on any=20
nearby metal water pipe, if one exists. Telephone, cable TV, and other=20
electrical services should also be ground connected together, at least =
at one=20
point on the property.</FONT></DIV>
<DIV><FONT face=3DArial size=3D2></FONT>&nbsp;</DIV>
<DIV><FONT face=3DArial size=3D2>Before the code required that a sub =
panel in an out=20
building&nbsp;had to be grounded via a separate ground rod, a 60' pine =
tree next=20
to my shop was&nbsp;struck by lightning (3' away). It was such a large =
strike=20
that the top 16' of this pine tree was blown off and fell to the=20
ground.&nbsp;The lightning&nbsp;also jumped from the tree trunk into the =
metal=20
face&nbsp;of the door and then up from the top corners of the door =
through the=20
1/2" plywood sofitting above the door into&nbsp;the armored electrical =
cabling=20
above the door (blew 1"X6" slots through the plywood). Although the =
electrical=20
panel in the shop was grounded via the&nbsp;service cable from the shop =
to the=20
main panel in the house, at the time&nbsp;I didn't have a separate =
ground rod=20
installed at the shop, as it wasn't required by code. The ground =
connection via=20
the electrical cable to the house aparently wasn't sufficient to carry =
the=20
lightning load&nbsp;because the&nbsp;lightning jumped between the ground =
and=20
neutral in the sub panel in the shop and&nbsp;went back to the main =
panel in the=20
house that way too. This resulted in a large burn mark in the sub panel =
and=20
burns between neutral and ground in many of the electrical&nbsp;outlet =
boxes=20
both inside the shop and the house.&nbsp;</FONT></DIV>
<DIV><FONT face=3DArial size=3D2></FONT>&nbsp;</DIV>
<DIV><FONT face=3DArial size=3D2>Four days later, while I was just =
sitting in the=20
shop looking at some plans on my workbench, the receptacle directly =
behind my=20
radial arm saw&nbsp;suddenly threw sparks and set fire to the wall =
around it.=20
Nothing electrical in the shop was running at the time, except for the =
overhead=20
lights, which are on a separate circuit. It's a good thing that I was=20
there.&nbsp; I was able to quickly shut off the power and use an =
extinguisher to=20
put out the fire on/in the wall. If I hadn't been sitting =
there&nbsp;when this=20
happened I would have lost my whole shop.</FONT></DIV>
<DIV>&nbsp;</DIV>
<DIV><FONT face=3DArial size=3D2>After this&nbsp;incident I replaced =
many of the=20
outlets in my shop and in my house, personally inspected all of them, =
and added=20
a ground rod to my shop panel wiring. I&nbsp;now frequently take the =
time (at=20
least once every spring) to check to be sure that my phone wiring, =
my&nbsp;cable=20
TV wiring,&nbsp;and my house electrical panels are all&nbsp;ground=20
connected&nbsp;to each other&nbsp;and to the ground =
rods.</FONT>&nbsp;<FONT=20
face=3DArial size=3D2>When I make this check I&nbsp;remove, clean, and =
replace any=20
connection that appears not to be perfect.</FONT></DIV>
<DIV><FONT face=3DArial size=3D2></FONT>&nbsp;</DIV>
<DIV><FONT face=3DArial size=3D2>I have always had a significant respect =
for=20
lightning, but this incident&nbsp;enhanced this respect=20
significantly.</FONT></DIV>
<DIV><FONT face=3DArial size=3D2></FONT><BR>-- <BR>Charley</DIV>
<DIV>&nbsp;</DIV>
<BLOCKQUOTE dir=3Dltr=20
style=3D"PADDING-RIGHT: 0px; PADDING-LEFT: 5px; MARGIN-LEFT: 5px; =
BORDER-LEFT: #000000 2px solid; MARGIN-RIGHT: 0px">
<DIV>"todd" &lt;<A =
href=3D"mailto:[email protected]">[email protected]</A>&gt;=20
wrote in message <A=20
=
href=3D"news:[email protected]">news:1LGdnRxiq=
[email protected]</A>...</DIV>
<DIV><FONT face=3DArial size=3D2>I recently built a new detached shop =
(the kind of=20
shop that my wife parks her van in).&nbsp; The electric service to the =
shop is=20
fed from the house via 240V 50A breaker.&nbsp; When I had the =
electrical=20
inspected, the inspector noted that since I had more than one circuit =
in the=20
shop subpanel, the subpanel needed its own ground rod.&nbsp; The =
electrian=20
came back and put the ground rod in and connected the wire from the =
ground rod=20
to the neutral bus.&nbsp; The inspector came back again and said that =
the wire=20
from the ground rod needed to be connected to the panel case instead =
of the=20
neutral.&nbsp; I figured I could take care of that quickly myself, but =
now I=20
have a question.&nbsp; There is a ground from the main panel that =
currently=20
connects to the panel case.&nbsp; Do I leave that in place when I =
connect the=20
wire from the new ground rod?&nbsp; In case a pic would help, here it =
is=20
before I moved the new ground wire off the neutral bus.</FONT></DIV>
<DIV>&nbsp;</DIV>
<DIV><A =
href=3D"http://www.freeimagehosting.net/uploads/0d19e399c3.jpg"><FONT=20
face=3DArial=20
=
size=3D2>http://www.freeimagehosting.net/uploads/0d19e399c3.jpg</FONT></A=
></DIV>
<P><FONT face=3DArial size=3D2>The bottom left conduit is the service =
from the=20
house with two hots, a neutral, and the ground wire.&nbsp; The conduit =
to the=20
right of that is the wire that connects to the ground rod (the wire is =
black,=20
but is marked as ground with green tape).&nbsp; I moved this wire to =
the=20
ground connection in the bottom middle of the box, but I don't know =
what to do=20
with the ground wire that is there now that connects back to the main=20
panel.</FONT></P>
<P><FONT face=3DArial =
size=3D2>todd</FONT></P></BLOCKQUOTE></BODY></HTML>

------=_NextPart_000_0011_01C738AD.B7B8FCC0--

Bb

"Bewildered"

in reply to "todd" on 15/01/2007 1:32 AM

15/01/2007 3:23 PM

That box looks almost exactly the same as a GE box I just bought to, also,
put a 50a subpanel in my shop; though you are further along than I am.
My box has a ground bus attached to the two back holes in the upper right.
All grounds, including the ones from your panel and grounding rod go to
that. If you don't have one, you have to buy one.
Actually, I don't see your circuit grounds, but maybe they just don't show
up in the picture.
I paid $32 at Lowes for my box with 6 breakers and the grounding bus
installed. How did you do?

sD

[email protected] (Doug Miller)

in reply to "todd" on 15/01/2007 1:32 AM

15/01/2007 12:41 PM

In article <[email protected]>, "todd" <[email protected]> wrote:

>I recently built a new detached shop (the kind of shop that my wife
>parks her van in). The electric service to the shop is fed from the
>house via 240V 50A breaker. When I had the electrical inspected, the
>inspector noted that since I had more than one circuit in the shop
>subpanel, the subpanel needed its own ground rod. The electrian came
>back and put the ground rod in and connected the wire from the ground
>rod to the neutral bus. The inspector came back again and said that the
>wire from the ground rod needed to be connected to the panel case
>instead of the neutral. I figured I could take care of that quickly
>myself, but now I have a question. There is a ground from the main
>panel that currently connects to the panel case. Do I leave that in
>place when I connect the wire from the new ground rod?

Yes.

> In case a pic
>would help, here it is before I moved the new ground wire off the
>neutral bus.
>
>http://www.freeimagehosting.net/uploads/0d19e399c3.jpg

The picture helps immensely.

>The bottom left conduit is the service from the house with two hots, a
>neutral, and the ground wire. The conduit to the right of that is the
>wire that connects to the ground rod (the wire is black, but is marked
>as ground with green tape). I moved this wire to the ground connection
>in the bottom middle of the box, but I don't know what to do with the
>ground wire that is there now that connects back to the main panel.
>
OK.... here's what you need to do: Install a separate grounding bus bar (maybe
ten bucks at the Borg). This will bolt directly to the panel chassis; no need
for a jumper.Then connect both the grounding wire from the main panel, and the
wire to your ground rod, to that bus bar. Done.

The panel probably already has a place ready-made for attaching such a bar.
Look for two or three raised bosses on the inside, either at the right or left
side (possibly both) with a tapped hole in the center of each one. Those are
your attachment points.

Alternatively, you could remove the bonding bar that connects the two bus bars
shown in the photo, and use the bar on the left as your grounding bus. Connect
the wires as above, and add a jumper to the panel chassis as well.

--
Regards,
Doug Miller (alphageek at milmac dot com)

It's time to throw all their damned tea in the harbor again.