25/07/2007 1:59 PM

Static pressure with 15' of 4" hose on a cyclone?

I am looking into buying a cyclone and have narrowed it down to 2.
One fan curve is almost flat, while the second is much higher at low static
pressures and much lower at high static pressures.
The second vender says the sharply sloping curve is more appropriate, as 15'
of 4" hose hooked to a jointer will be about 4" of static pressure.
Based on what I have read in the past, I would have expected it to be more
like 8 or 9", and the flat curve is much better there. So, the superior
unit depends on how much static pressure I will be seeing.
Can anyone point me to documentation on this?


This topic has 2 replies

TT

"Toller"

in reply to "Toller" on 25/07/2007 1:59 PM

25/07/2007 2:12 PM

and got a static pressure of 9.4" for 15' of 4" hose, but that thing is
confusing, so I might not have been doing it right...
"Toller" <[email protected]> wrote in message
news:[email protected]...
>I am looking into buying a cyclone and have narrowed it down to 2.
> One fan curve is almost flat, while the second is much higher at low
> static pressures and much lower at high static pressures.
> The second vender says the sharply sloping curve is more appropriate, as
> 15' of 4" hose hooked to a jointer will be about 4" of static pressure.
> Based on what I have read in the past, I would have expected it to be more
> like 8 or 9", and the flat curve is much better there. So, the superior
> unit depends on how much static pressure I will be seeing.
> Can anyone point me to documentation on this?
>

dn

dpb

in reply to "Toller" on 25/07/2007 1:59 PM

25/07/2007 1:23 PM

Toller wrote:

...[top posting repaired]...

> "Toller" <[email protected]> wrote in message
> news:[email protected]...
>> I am looking into buying a cyclone and have narrowed it down to 2.
>> One fan curve is almost flat, while the second is much higher at low
>> static pressures and much lower at high static pressures.
>> The second vender says the sharply sloping curve is more appropriate, as
>> 15' of 4" hose hooked to a jointer will be about 4" of static pressure.
>> Based on what I have read in the past, I would have expected it to be more
>> like 8 or 9", and the flat curve is much better there. So, the superior
>> unit depends on how much static pressure I will be seeing.
>> Can anyone point me to documentation on this?
>>
> and got a static pressure of 9.4" for 15' of 4" hose, but that thing
> is confusing, so I might not have been doing it right...

Depends on whether you're talking flex hose or straight wall pipe/hose.
4" sounds about right for smooth wall, 8-9" for flex hose of that length.

Unless you have a fixed path and distance, it'll vary anyway as you move
the hose. If it is fixed location, I'd recommend ditching the flex hose
for anything except the shortest run possible as connection, maybe.

--


You’ve reached the end of replies