BB

Bill

08/06/2016 3:05 PM

Installing (2002) Delta TS

In the owner's manual for my (new to me) Delta TS (36-841), it says:

"This circuit should not be less than #12 wire and should be protected
with a 20 Amp time lag fuse."

Not being aware of this detail until now, I was just going to use a
regular 20-Amp circuit-breaker (I ran #12 wire). Please advise. Thank you!

Bill


This topic has 52 replies

SW

Spalted Walt

in reply to Bill on 08/06/2016 3:05 PM

08/06/2016 8:53 PM

Bill <[email protected]> wrote:

>
>>> Bill wrote:
>>>> In the owner's manual for my (new to me) Delta TS (36-841), it says:
>>>>
>>>> "This circuit should not be less than #12 wire and should be
>>>> protected with a 20 Amp time lag fuse."
>>>>
>>>> Not being aware of this detail until now, I was just going to use a
>>>> regular 20-Amp circuit-breaker (I ran #12 wire).
>>>
>>> Correction, I ran #10 wire, for this.
>> Also when I say "regular", I do mean 240v (2-pole).
>>
>> Thanks!
>> Bill
>>
>> Please advise. Thank you!
>
>In trying to answer my question, I learned that
>"all circuit breakers are "time delay" by nature of their design."
>
>So, I guess we'll see what happens...
>
>Progress in the shop is continuing after a delay or two in recent years
>caused by major events.
>
>Bill

Congratulations, Bill! I've had my Unisaw (Delta 36-844) for 6 years
and have had no problems with #12 Romex (about 15ft from sub-panel)
and this (standard?) Siemens breaker:

http://www.homedepot.com/p/Siemens-20-Amp-Double-Pole-Type-QP-Circuit-Breaker-Q220U/100074746

Sc

Sonny

in reply to Bill on 08/06/2016 3:05 PM

09/06/2016 7:16 PM

On Thursday, June 9, 2016 at 9:12:36 PM UTC-5, krw wrote:

>
> Does the Australian electricity turn the other way?

Ugh..., Yes!

Sonny

kk

krw

in reply to Bill on 08/06/2016 3:05 PM

08/06/2016 11:06 PM

On Wed, 8 Jun 2016 19:48:35 -0700 (PDT), Bob Villa
<[email protected]> wrote:

>On Wednesday, June 8, 2016 at 8:55:19 PM UTC-5, Markem wrote:
>> On Wed, 8 Jun 2016 21:30:09 -0400, Mike Marlow
>> <[email protected]> wrote:
>>
>> >Markem wrote:
>> >> On Wed, 8 Jun 2016 15:19:50 -0400, FrozenNorth
>> >> <[email protected]> wrote:
>> >>
>> >>> On 2016-06-08 3:07 PM, Bill wrote:
>> >>>> Bill wrote:
>> >>>>> In the owner's manual for my (new to me) Delta TS (36-841), it says:
>> >>>>>
>> >>>>> "This circuit should not be less than #12 wire and should be protected
>> >>>>> with a 20 Amp time lag fuse."
>> >>>>>
>> >>>>> Not being aware of this detail until now, I was just going to use a
>> >>>>> regular 20-Amp circuit-breaker (I ran #12 wire).
>> >>>>
>> >>>> Correction, I ran #10 wire, for this.
>> >>>>
>> >>>>
>> >>>>> Please advise. Thank you!
>> >>>>>
>> >>>>> Bill
>> >>>>
>> >>> Prepare for a few breaker pops, hope the fuse panel is close to the saw.
>> >>
>> >> If wired for 120 V I would say yes, if wire for 240 V probably not.
>> >>
>> >
>> >20 amps is 20 amps. Don't matter whether you're running 120 or 240.
>>
>> Yes but a 240 V circuit has two 20 amp leads, a motor drawing 20 amps,
>> 10 per leg.
>>
>> Mark
>
>Current (when there is a load) is the same at any place in the circuit, regardless of being 120 or 240.

Yes, in the circuit external to the motor but not if the motor itself
is considered. The voltage across each winding is 120V and the
current in each is 10A, whether it's wired as 120V (parallel windings)
or 240V (series).

Sc

Sonny

in reply to Bill on 08/06/2016 3:05 PM

09/06/2016 5:42 AM

On Thursday, June 9, 2016 at 7:19:16 AM UTC-5, Swingman wrote:
> On 6/8/2016 2:07 PM, Bill wrote:
> > Bill wrote:
> >> In the owner's manual for my (new to me) Delta TS (36-841), it says:
> >>
> >> "This circuit should not be less than #12 wire and should be protected
> >> with a 20 Amp time lag fuse."
> >>
> >> Not being aware of this detail until now, I was just going to use a
> >> regular 20-Amp circuit-breaker (I ran #12 wire).
> >
> > Correction, I ran #10 wire, for this.
>
> Have at it, you're set to make sawdust ... no further need for bits and
> bytes.
>

.... Unless he's using Austrailian electricity or has a Canadian saw/sideways breaker box!?

Sonny

BV

Bob Villa

in reply to Bill on 08/06/2016 3:05 PM

09/06/2016 7:14 PM

On Thursday, June 9, 2016 at 7:55:57 PM UTC-5, Bill wrote:
> Bob Villa wrote:
> > On Thursday, June 9, 2016 at 4:58:37 PM UTC-5, Bill wrote:
> >> Leon wrote:
> >>> On 6/9/2016 4:23 PM, Bill wrote:
> >>>> Bob Villa wrote:
> >>>>> Even though this is not DC...Ohm's Law says your theory is wrong.
> >>>>> I=3DE/R, if you double the voltage you halve the current. Also, wat=
tage
> >>>>> would prove that out. The same motor wired 240, would draw
> >>>> I get it. I'm also gently reminded/informed that a 240V circuit is =
Not
> >>>> the equivalent of two 120v circuits.
> >>>
> >>> But you do realize that the 240 in your home is made up of 2 out of
> >>> phase 120 circuits...
> >>>
> >> Yes, that's most-surely what led to my confusion about the way a 240v
> >> circuit works...
> >> So, a 240v circuit apparently doesn't have a direction....or rather, i=
t
> >> has 2 directions at the same time, from one leg to another, and vice-v=
ersa.
> >>
> >> Bill
> > ...half of your 120 volt circuits would be out of phase with the other =
half. And there are 120 direction changes (60 cycles) in one second.
>=20
> I get it! Thanks! Am I the only one here who didn't know that? :)
>=20
> Bill

( =CD=A1~ =CD=9C=CA=96 =CD=A1=C2=B0)

BV

Bob Villa

in reply to Bill on 08/06/2016 3:05 PM

09/06/2016 6:07 AM

On Thursday, June 9, 2016 at 1:45:41 AM UTC-5, Bill wrote:
> J. Clarke wrote:
> > In article <[email protected]>,
> > [email protected] says...
> >> On Wednesday, June 8, 2016 at 8:55:19 PM UTC-5, Markem wrote:
> >>> On Wed, 8 Jun 2016 21:30:09 -0400, Mike Marlow
> >>> <[email protected]> wrote:
> >>>
> >>>> Markem wrote:
> >>>>> On Wed, 8 Jun 2016 15:19:50 -0400, FrozenNorth
> >>>>> <[email protected]> wrote:
> >>>>>
> >>>>>> On 2016-06-08 3:07 PM, Bill wrote:
> >>>>>>> Bill wrote:
> >>>>>>>> In the owner's manual for my (new to me) Delta TS (36-841), it s=
ays:
> >>>>>>>>
> >>>>>>>> "This circuit should not be less than #12 wire and should be pro=
tected
> >>>>>>>> with a 20 Amp time lag fuse."
> >>>>>>>>
> >>>>>>>> Not being aware of this detail until now, I was just going to us=
e a
> >>>>>>>> regular 20-Amp circuit-breaker (I ran #12 wire).
> >>>>>>> Correction, I ran #10 wire, for this.
> >>>>>>>
> >>>>>>>
> >>>>>>>> Please advise. Thank you!
> >>>>>>>>
> >>>>>>>> Bill
> >>>>>> Prepare for a few breaker pops, hope the fuse panel is close to th=
e saw.
> >>>>> If wired for 120 V I would say yes, if wire for 240 V probably not.
> >>>>>
> >>>> 20 amps is 20 amps. Don't matter whether you're running 120 or 240.
> >>> Yes but a 240 V circuit has two 20 amp leads, a motor drawing 20 amps=
,
> >>> 10 per leg.
> >>>
> >>> Mark
> >> Current (when there is a load) is the same at any place in the circuit=
, regardless of being 120 or 240.
> > However a more that needs 20 amps at 110 volts only needs 10 at 220.
> That's because it gets 10 amps on Each of Two legs at the same time (I=20
> think "legs" is the right word, I could be wrong).

Even though this is not DC...Ohm's Law says your theory is wrong. I=3DE/R, =
if you double the voltage you halve the current. Also, wattage would prove =
that out. The same motor wired 240, would draw half what it did on 120. On =
single phase, the neutral (white or ground) is the center-tap of the power =
transformer. That's why it's half the voltage.

BV

Bob Villa

in reply to Bill on 08/06/2016 3:05 PM

09/06/2016 3:37 PM

On Thursday, June 9, 2016 at 4:58:37 PM UTC-5, Bill wrote:
> Leon wrote:
> > On 6/9/2016 4:23 PM, Bill wrote:
> >> Bob Villa wrote:
> >>> Even though this is not DC...Ohm's Law says your theory is wrong.
> >>> I=E/R, if you double the voltage you halve the current. Also, wattage
> >>> would prove that out. The same motor wired 240, would draw
> >>
> >> I get it. I'm also gently reminded/informed that a 240V circuit is Not
> >> the equivalent of two 120v circuits.
> >
> >
> > But you do realize that the 240 in your home is made up of 2 out of
> > phase 120 circuits...
> >
>
> Yes, that's most-surely what led to my confusion about the way a 240v
> circuit works...
> So, a 240v circuit apparently doesn't have a direction....or rather, it
> has 2 directions at the same time, from one leg to another, and vice-versa.
>
> Bill

...half of your 120 volt circuits would be out of phase with the other half. And there are 120 direction changes (60 cycles) in one second.

Pp

Puckdropper

in reply to Bill on 08/06/2016 3:05 PM

09/06/2016 2:58 AM

krw <[email protected]> wrote in news:ghkhlbpfmnljfsti8b697rab3upu9593ap@
4ax.com:

>
> There are a bunch of woodworking EEs. ;-) It seems the two
> disciplines use some of the same mental skills.
>

Looks like you're on to something.
- Sparks flying is a bad thing.
- You can glue/solder pieces together, but it's not always a good idea.
- You can never have too many clamps/outlets.
- Measure twice, cut once applies to electricity too. (Measure, power good,
cut off at breaker, measure again, no power, probably safe to work.)
- You don't have to match colors to make things work, but not doing so is
the sure sign of a clueless hack. (Intentional mismatching is ok.)
- Hand planes and wire strippers remove the outer surface of the workpiece.
- Copper turns green with age, so do trees.
- Running the wood backwards through the saw won't reattach it... Not even
if you swap the motor leads.
- The sun can be used to generate wood or electricity.

kk

krw

in reply to Bill on 08/06/2016 3:05 PM

08/06/2016 8:17 PM

On Wed, 8 Jun 2016 15:07:57 -0400, Bill <[email protected]>
wrote:

>Bill wrote:
>> In the owner's manual for my (new to me) Delta TS (36-841), it says:
>>
>> "This circuit should not be less than #12 wire and should be protected
>> with a 20 Amp time lag fuse."
>>
>> Not being aware of this detail until now, I was just going to use a
>> regular 20-Amp circuit-breaker (I ran #12 wire).
>
>Correction, I ran #10 wire, for this.
>
You may want to put a 30A breaker on it. In any case, be sure the
breaker you use is "listed" for the wire you're using.

BV

Bob Villa

in reply to Bill on 08/06/2016 3:05 PM

08/06/2016 7:48 PM

On Wednesday, June 8, 2016 at 8:55:19 PM UTC-5, Markem wrote:
> On Wed, 8 Jun 2016 21:30:09 -0400, Mike Marlow
> <[email protected]> wrote:
>
> >Markem wrote:
> >> On Wed, 8 Jun 2016 15:19:50 -0400, FrozenNorth
> >> <[email protected]> wrote:
> >>
> >>> On 2016-06-08 3:07 PM, Bill wrote:
> >>>> Bill wrote:
> >>>>> In the owner's manual for my (new to me) Delta TS (36-841), it says:
> >>>>>
> >>>>> "This circuit should not be less than #12 wire and should be protected
> >>>>> with a 20 Amp time lag fuse."
> >>>>>
> >>>>> Not being aware of this detail until now, I was just going to use a
> >>>>> regular 20-Amp circuit-breaker (I ran #12 wire).
> >>>>
> >>>> Correction, I ran #10 wire, for this.
> >>>>
> >>>>
> >>>>> Please advise. Thank you!
> >>>>>
> >>>>> Bill
> >>>>
> >>> Prepare for a few breaker pops, hope the fuse panel is close to the saw.
> >>
> >> If wired for 120 V I would say yes, if wire for 240 V probably not.
> >>
> >
> >20 amps is 20 amps. Don't matter whether you're running 120 or 240.
>
> Yes but a 240 V circuit has two 20 amp leads, a motor drawing 20 amps,
> 10 per leg.
>
> Mark

Current (when there is a load) is the same at any place in the circuit, regardless of being 120 or 240.

JC

"J. Clarke"

in reply to Bill on 08/06/2016 3:05 PM

09/06/2016 2:10 AM

In article <[email protected]>,
[email protected] says...
>
> On Wednesday, June 8, 2016 at 8:55:19 PM UTC-5, Markem wrote:
> > On Wed, 8 Jun 2016 21:30:09 -0400, Mike Marlow
> > <[email protected]> wrote:
> >
> > >Markem wrote:
> > >> On Wed, 8 Jun 2016 15:19:50 -0400, FrozenNorth
> > >> <[email protected]> wrote:
> > >>
> > >>> On 2016-06-08 3:07 PM, Bill wrote:
> > >>>> Bill wrote:
> > >>>>> In the owner's manual for my (new to me) Delta TS (36-841), it says:
> > >>>>>
> > >>>>> "This circuit should not be less than #12 wire and should be protected
> > >>>>> with a 20 Amp time lag fuse."
> > >>>>>
> > >>>>> Not being aware of this detail until now, I was just going to use a
> > >>>>> regular 20-Amp circuit-breaker (I ran #12 wire).
> > >>>>
> > >>>> Correction, I ran #10 wire, for this.
> > >>>>
> > >>>>
> > >>>>> Please advise. Thank you!
> > >>>>>
> > >>>>> Bill
> > >>>>
> > >>> Prepare for a few breaker pops, hope the fuse panel is close to the saw.
> > >>
> > >> If wired for 120 V I would say yes, if wire for 240 V probably not.
> > >>
> > >
> > >20 amps is 20 amps. Don't matter whether you're running 120 or 240.
> >
> > Yes but a 240 V circuit has two 20 amp leads, a motor drawing 20 amps,
> > 10 per leg.
> >
> > Mark
>
> Current (when there is a load) is the same at any place in the circuit, regardless of being 120 or 240.

However a more that needs 20 amps at 110 volts only needs 10 at 220.

JC

"J. Clarke"

in reply to Bill on 08/06/2016 3:05 PM

11/06/2016 5:54 AM

In article <[email protected]>,
[email protected] says...
>
> Bill <[email protected]> wrote in news:[email protected]:
>
> > In the owner's manual for my (new to me) Delta TS (36-841), it says:
> >
> > "This circuit should not be less than #12 wire and should be protected
> > with a 20 Amp time lag fuse."
> >
> > Not being aware of this detail until now, I was just going to use a
> > regular 20-Amp circuit-breaker (I ran #12 wire). Please advise. Thank you!
> >
> 20 amp circuit breaker is fine.

The breaker equivalent of a "slow-blow" fuse is called a "high
magnetic" breaker. If your regular breaker is tripping on startup you
might want to consider going that route. Personally when I run into tht
though I generally just rewire the tool for 220 (if that's an option)
and run a dedicated circuit. Most tools seem happier with 220 anyway.

DM

Doug Miller

in reply to Bill on 08/06/2016 3:05 PM

09/06/2016 6:56 PM

Bill <[email protected]> wrote in news:[email protected]:

> In the owner's manual for my (new to me) Delta TS (36-841), it says:
>
> "This circuit should not be less than #12 wire and should be protected
> with a 20 Amp time lag fuse."
>
> Not being aware of this detail until now, I was just going to use a
> regular 20-Amp circuit-breaker (I ran #12 wire). Please advise. Thank you!
>
20 amp circuit breaker is fine.

Ll

Leon

in reply to Bill on 08/06/2016 3:05 PM

09/06/2016 4:47 PM

On 6/9/2016 4:23 PM, Bill wrote:
> Bob Villa wrote:
>> On Thursday, June 9, 2016 at 1:45:41 AM UTC-5, Bill wrote:
>>> J. Clarke wrote:
>>>> In article <[email protected]>,
>>>> [email protected] says...
>>>>> On Wednesday, June 8, 2016 at 8:55:19 PM UTC-5, Markem wrote:
>>>>>> On Wed, 8 Jun 2016 21:30:09 -0400, Mike Marlow
>>>>>> <[email protected]> wrote:
>>>>>>
>>>>>>> Markem wrote:
>>>>>>>> On Wed, 8 Jun 2016 15:19:50 -0400, FrozenNorth
>>>>>>>> <[email protected]> wrote:
>>>>>>>>
>>>>>>>>> On 2016-06-08 3:07 PM, Bill wrote:
>>>>>>>>>> Bill wrote:
>>>>>>>>>>> In the owner's manual for my (new to me) Delta TS (36-841),
>>>>>>>>>>> it says:
>>>>>>>>>>>
>>>>>>>>>>> "This circuit should not be less than #12 wire and should be
>>>>>>>>>>> protected
>>>>>>>>>>> with a 20 Amp time lag fuse."
>>>>>>>>>>>
>>>>>>>>>>> Not being aware of this detail until now, I was just going to
>>>>>>>>>>> use a
>>>>>>>>>>> regular 20-Amp circuit-breaker (I ran #12 wire).
>>>>>>>>>> Correction, I ran #10 wire, for this.
>>>>>>>>>>
>>>>>>>>>>
>>>>>>>>>>> Please advise. Thank you!
>>>>>>>>>>>
>>>>>>>>>>> Bill
>>>>>>>>> Prepare for a few breaker pops, hope the fuse panel is close to
>>>>>>>>> the saw.
>>>>>>>> If wired for 120 V I would say yes, if wire for 240 V probably not.
>>>>>>>>
>>>>>>> 20 amps is 20 amps. Don't matter whether you're running 120 or 240.
>>>>>> Yes but a 240 V circuit has two 20 amp leads, a motor drawing 20
>>>>>> amps,
>>>>>> 10 per leg.
>>>>>>
>>>>>> Mark
>>>>> Current (when there is a load) is the same at any place in the
>>>>> circuit, regardless of being 120 or 240.
>>>> However a more that needs 20 amps at 110 volts only needs 10 at 220.
>>> That's because it gets 10 amps on Each of Two legs at the same time (I
>>> think "legs" is the right word, I could be wrong).
>> Even though this is not DC...Ohm's Law says your theory is wrong.
>> I=E/R, if you double the voltage you halve the current. Also, wattage
>> would prove that out. The same motor wired 240, would draw
>
> I get it. I'm also gently reminded/informed that a 240V circuit is Not
> the equivalent of two 120v circuits.


But you do realize that the 240 in your home is made up of 2 out of
phase 120 circuits...

Sk

Swingman

in reply to Bill on 08/06/2016 3:05 PM

09/06/2016 7:18 AM

On 6/8/2016 2:07 PM, Bill wrote:
> Bill wrote:
>> In the owner's manual for my (new to me) Delta TS (36-841), it says:
>>
>> "This circuit should not be less than #12 wire and should be protected
>> with a 20 Amp time lag fuse."
>>
>> Not being aware of this detail until now, I was just going to use a
>> regular 20-Amp circuit-breaker (I ran #12 wire).
>
> Correction, I ran #10 wire, for this.

Have at it, you're set to make sawdust ... no further need for bits and
bytes.

--
eWoodShop: www.eWoodShop.com
Wood Shop: www.e-WoodShop.net
https://www.google.com/+eWoodShop
https://plus.google.com/+KarlCaillouet/posts
http://www.custommade.com/by/ewoodshop/
https://www.facebook.com/eWoodShop-206166666122228
KarlCaillouet@ (the obvious)

Mm

Markem

in reply to Bill on 08/06/2016 3:05 PM

08/06/2016 7:37 PM

On Wed, 8 Jun 2016 15:19:50 -0400, FrozenNorth
<[email protected]> wrote:

>On 2016-06-08 3:07 PM, Bill wrote:
>> Bill wrote:
>>> In the owner's manual for my (new to me) Delta TS (36-841), it says:
>>>
>>> "This circuit should not be less than #12 wire and should be protected
>>> with a 20 Amp time lag fuse."
>>>
>>> Not being aware of this detail until now, I was just going to use a
>>> regular 20-Amp circuit-breaker (I ran #12 wire).
>>
>> Correction, I ran #10 wire, for this.
>>
>>
>>> Please advise. Thank you!
>>>
>>> Bill
>>
>Prepare for a few breaker pops, hope the fuse panel is close to the saw.

If wired for 120 V I would say yes, if wire for 240 V probably not.

Mark

kk

krw

in reply to Bill on 08/06/2016 3:05 PM

09/06/2016 10:10 PM

On Thu, 9 Jun 2016 17:23:47 -0400, Bill <[email protected]>
wrote:

>Bob Villa wrote:
>> On Thursday, June 9, 2016 at 1:45:41 AM UTC-5, Bill wrote:
>>> J. Clarke wrote:
>>>> In article <[email protected]>,
>>>> [email protected] says...
>>>>> On Wednesday, June 8, 2016 at 8:55:19 PM UTC-5, Markem wrote:
>>>>>> On Wed, 8 Jun 2016 21:30:09 -0400, Mike Marlow
>>>>>> <[email protected]> wrote:
>>>>>>
>>>>>>> Markem wrote:
>>>>>>>> On Wed, 8 Jun 2016 15:19:50 -0400, FrozenNorth
>>>>>>>> <[email protected]> wrote:
>>>>>>>>
>>>>>>>>> On 2016-06-08 3:07 PM, Bill wrote:
>>>>>>>>>> Bill wrote:
>>>>>>>>>>> In the owner's manual for my (new to me) Delta TS (36-841), it says:
>>>>>>>>>>>
>>>>>>>>>>> "This circuit should not be less than #12 wire and should be protected
>>>>>>>>>>> with a 20 Amp time lag fuse."
>>>>>>>>>>>
>>>>>>>>>>> Not being aware of this detail until now, I was just going to use a
>>>>>>>>>>> regular 20-Amp circuit-breaker (I ran #12 wire).
>>>>>>>>>> Correction, I ran #10 wire, for this.
>>>>>>>>>>
>>>>>>>>>>
>>>>>>>>>>> Please advise. Thank you!
>>>>>>>>>>>
>>>>>>>>>>> Bill
>>>>>>>>> Prepare for a few breaker pops, hope the fuse panel is close to the saw.
>>>>>>>> If wired for 120 V I would say yes, if wire for 240 V probably not.
>>>>>>>>
>>>>>>> 20 amps is 20 amps. Don't matter whether you're running 120 or 240.
>>>>>> Yes but a 240 V circuit has two 20 amp leads, a motor drawing 20 amps,
>>>>>> 10 per leg.
>>>>>>
>>>>>> Mark
>>>>> Current (when there is a load) is the same at any place in the circuit, regardless of being 120 or 240.
>>>> However a more that needs 20 amps at 110 volts only needs 10 at 220.
>>> That's because it gets 10 amps on Each of Two legs at the same time (I
>>> think "legs" is the right word, I could be wrong).
>> Even though this is not DC...Ohm's Law says your theory is wrong. I=E/R, if you double the voltage you halve the current. Also, wattage would prove that out. The same motor wired 240, would draw
>
>I get it. I'm also gently reminded/informed that a 240V circuit is Not
>the equivalent of two 120v circuits.

It is, really, except that the two circuits are out of phase, so they
add (if they were in-phase, they'd subtract).

>Thanks,
>Bill
>
>
>> half what it did on 120. On single phase, the neutral (white or ground) is the center-tap of the power transformer. That's why it's half the voltage.


Yes, on the pole, and the neutral is brought into the panel. However,
there is no neutral in this (240V) circuit. It's not needed because
the saw doesn't use 120V (if wired for 240V).

Mm

Markem

in reply to Bill on 08/06/2016 3:05 PM

08/06/2016 8:55 PM

On Wed, 8 Jun 2016 21:30:09 -0400, Mike Marlow
<[email protected]> wrote:

>Markem wrote:
>> On Wed, 8 Jun 2016 15:19:50 -0400, FrozenNorth
>> <[email protected]> wrote:
>>
>>> On 2016-06-08 3:07 PM, Bill wrote:
>>>> Bill wrote:
>>>>> In the owner's manual for my (new to me) Delta TS (36-841), it says:
>>>>>
>>>>> "This circuit should not be less than #12 wire and should be protected
>>>>> with a 20 Amp time lag fuse."
>>>>>
>>>>> Not being aware of this detail until now, I was just going to use a
>>>>> regular 20-Amp circuit-breaker (I ran #12 wire).
>>>>
>>>> Correction, I ran #10 wire, for this.
>>>>
>>>>
>>>>> Please advise. Thank you!
>>>>>
>>>>> Bill
>>>>
>>> Prepare for a few breaker pops, hope the fuse panel is close to the saw.
>>
>> If wired for 120 V I would say yes, if wire for 240 V probably not.
>>
>
>20 amps is 20 amps. Don't matter whether you're running 120 or 240.

Yes but a 240 V circuit has two 20 amp leads, a motor drawing 20 amps,
10 per leg.

Mark

Sc

Sonny

in reply to Bill on 08/06/2016 3:05 PM

09/06/2016 7:13 PM

On Thursday, June 9, 2016 at 7:55:57 PM UTC-5, Bill wrote:

>
> I get it! Thanks! Am I the only one here who didn't know that? :)
>
> Bill

Me. I'm probably qualified for an honorary degree in Electrical Ignorance.

Sonny

kk

krw

in reply to Bill on 08/06/2016 3:05 PM

08/06/2016 8:24 PM

On Wed, 8 Jun 2016 15:19:50 -0400, FrozenNorth
<[email protected]> wrote:

>On 2016-06-08 3:07 PM, Bill wrote:
>> Bill wrote:
>>> In the owner's manual for my (new to me) Delta TS (36-841), it says:
>>>
>>> "This circuit should not be less than #12 wire and should be protected
>>> with a 20 Amp time lag fuse."
>>>
>>> Not being aware of this detail until now, I was just going to use a
>>> regular 20-Amp circuit-breaker (I ran #12 wire).
>>
>> Correction, I ran #10 wire, for this.
>>
>>
>>> Please advise. Thank you!
>>>
>>> Bill
>>
>Prepare for a few breaker pops, hope the fuse panel is close to the saw.

Nonsense. My 3HP Unisaur has been on a 20A (240V) circuit, with
20-30' of 12-2 W/G between it and the panel for years, with zero
trips. Come to think of it, it was ~50' in my last house.

kk

krw

in reply to Bill on 08/06/2016 3:05 PM

08/06/2016 10:22 PM

On Wed, 8 Jun 2016 21:58:58 -0400, Bill <[email protected]>
wrote:

>krw wrote:
>> dpb <[email protected]> wrote:
>>
>>> -MIKE- wrote:
>>>
>
>The OP is satisfied. I just bought a outlet to match the saw's male
>connector.

You done good.

>There's nothing like an electrical thread to create action around here.
>Thank you for your willingness to help!

There are a bunch of woodworking EEs. ;-) It seems the two
disciplines use some of the same mental skills.


Ll

Leon

in reply to Bill on 08/06/2016 3:05 PM

10/06/2016 8:46 AM

On 6/9/2016 7:55 PM, Bill wrote:
> Bob Villa wrote:
>> On Thursday, June 9, 2016 at 4:58:37 PM UTC-5, Bill wrote:
>>> Leon wrote:
>>>> On 6/9/2016 4:23 PM, Bill wrote:
>>>>> Bob Villa wrote:
>>>>>> Even though this is not DC...Ohm's Law says your theory is wrong.
>>>>>> I=E/R, if you double the voltage you halve the current. Also, wattage
>>>>>> would prove that out. The same motor wired 240, would draw
>>>>> I get it. I'm also gently reminded/informed that a 240V circuit is
>>>>> Not
>>>>> the equivalent of two 120v circuits.
>>>>
>>>> But you do realize that the 240 in your home is made up of 2 out of
>>>> phase 120 circuits...
>>>>
>>> Yes, that's most-surely what led to my confusion about the way a 240v
>>> circuit works...
>>> So, a 240v circuit apparently doesn't have a direction....or rather, it
>>> has 2 directions at the same time, from one leg to another, and
>>> vice-versa.
>>>
>>> Bill
>> ...half of your 120 volt circuits would be out of phase with the other
>> half. And there are 120 direction changes (60 cycles) in one second.
>
> I get it! Thanks! Am I the only one here who didn't know that? :)
>
> Bill
>
>


No, most don't get it, just regurgitating something they have googled. ;~)

kk

krw

in reply to Bill on 08/06/2016 3:05 PM

09/06/2016 10:14 PM

On 09 Jun 2016 02:58:34 GMT, Puckdropper
<puckdropper(at)yahoo(dot)com> wrote:

>krw <[email protected]> wrote in news:ghkhlbpfmnljfsti8b697rab3upu9593ap@
>4ax.com:
>
>>
>> There are a bunch of woodworking EEs. ;-) It seems the two
>> disciplines use some of the same mental skills.
>>
>
>Looks like you're on to something.
>- Sparks flying is a bad thing.
>- You can glue/solder pieces together, but it's not always a good idea.
>- You can never have too many clamps/outlets.
>- Measure twice, cut once applies to electricity too. (Measure, power good,
>cut off at breaker, measure again, no power, probably safe to work.)
>- You don't have to match colors to make things work, but not doing so is
>the sure sign of a clueless hack. (Intentional mismatching is ok.)
>- Hand planes and wire strippers remove the outer surface of the workpiece.
>- Copper turns green with age, so do trees.
>- Running the wood backwards through the saw won't reattach it... Not even
>if you swap the motor leads.
>- The sun can be used to generate wood or electricity.

;-)

However, there are differences. Wood can be used to make electricity
but the other way around takes a *long* time.

kk

krw

in reply to Bill on 08/06/2016 3:05 PM

08/06/2016 8:27 PM

On Wed, 08 Jun 2016 16:43:23 -0500, dpb <[email protected]> wrote:

>On 06/08/2016 3:59 PM, -MIKE- wrote:
>...
>
>> Old fuses would blow with the initial spike of current when saw motor
>> kicked on.
>
>"Fast-acting" ones, yes, "slo-blo" (specifically designed for motor
>loads and the like with an initial short-lived high-current transient)
>wouldn't.
>
>> A modern circuit breaker needs to heat up to trip (except in the case of
>> a short) so it can't get hot enough to trip from the very short current
>> spike of the motor's start-up.
>...
>
>The fuse had to heat up, too (in fact, it had to actually melt) but the
>idea is correct; they are designed to handle motoin adr loads inherently to
>be general-purpose; it would be a real pain to have to have separate
>breakers for the application.
>
>The time for a dead short to heat up and trip will be quite a lot
>shorter than that for the motor start; while a motor start is a
>(relatively) high current (say 3X or so of full load), that of a dead
>short is I=V/(R-->zero) --> Infinite.

No, in addition to the thermal detector, circuit breakers have a
magnetic trip. A high enough current will trip the circuit before the
thermal detector can trip.

BB

Bill

in reply to Bill on 08/06/2016 3:05 PM

08/06/2016 3:07 PM

Bill wrote:
> In the owner's manual for my (new to me) Delta TS (36-841), it says:
>
> "This circuit should not be less than #12 wire and should be protected
> with a 20 Amp time lag fuse."
>
> Not being aware of this detail until now, I was just going to use a
> regular 20-Amp circuit-breaker (I ran #12 wire).

Correction, I ran #10 wire, for this.


> Please advise. Thank you!
>
> Bill

Ff

FrozenNorth

in reply to Bill on 08/06/2016 3:05 PM

08/06/2016 3:19 PM

On 2016-06-08 3:07 PM, Bill wrote:
> Bill wrote:
>> In the owner's manual for my (new to me) Delta TS (36-841), it says:
>>
>> "This circuit should not be less than #12 wire and should be protected
>> with a 20 Amp time lag fuse."
>>
>> Not being aware of this detail until now, I was just going to use a
>> regular 20-Amp circuit-breaker (I ran #12 wire).
>
> Correction, I ran #10 wire, for this.
>
>
>> Please advise. Thank you!
>>
>> Bill
>
Prepare for a few breaker pops, hope the fuse panel is close to the saw.

--
Froz....

---
This email has been checked for viruses by Avast antivirus software.
https://www.avast.com/antivirus

kk

krw

in reply to FrozenNorth on 08/06/2016 3:19 PM

09/06/2016 10:55 PM

On Thu, 9 Jun 2016 22:35:29 -0400, Bill <[email protected]>
wrote:

>krw wrote:
>> On Thu, 9 Jun 2016 17:23:47 -0400, Bill <[email protected]>
>> wrote:
>>
>>> Bob Villa wrote:
>>>> On Thursday, June 9, 2016 at 1:45:41 AM UTC-5, Bill wrote:
>>>>> J. Clarke wrote:
>>>>>> In article <[email protected]>,
>>>>>> [email protected] says...
>>>>>>> On Wednesday, June 8, 2016 at 8:55:19 PM UTC-5, Markem wrote:
>>>>>>>> On Wed, 8 Jun 2016 21:30:09 -0400, Mike Marlow
>>>>>>>> <[email protected]> wrote:
>>>>>>>>
>>>>>>>>> Markem wrote:
>>>>>>>>>> On Wed, 8 Jun 2016 15:19:50 -0400, FrozenNorth
>>>>>>>>>> <[email protected]> wrote:
>>>>>>>>>>
>>>>>>>>>>> On 2016-06-08 3:07 PM, Bill wrote:
>>>>>>>>>>>> Bill wrote:
>>>>>>>>>>>>> In the owner's manual for my (new to me) Delta TS (36-841), it says:
>>>>>>>>>>>>>
>>>>>>>>>>>>> "This circuit should not be less than #12 wire and should be protected
>>>>>>>>>>>>> with a 20 Amp time lag fuse."
>>>>>>>>>>>>>
>>>>>>>>>>>>> Not being aware of this detail until now, I was just going to use a
>>>>>>>>>>>>> regular 20-Amp circuit-breaker (I ran #12 wire).
>>>>>>>>>>>> Correction, I ran #10 wire, for this.
>>>>>>>>>>>>
>>>>>>>>>>>>
>>>>>>>>>>>>> Please advise. Thank you!
>>>>>>>>>>>>>
>>>>>>>>>>>>> Bill
>>>>>>>>>>> Prepare for a few breaker pops, hope the fuse panel is close to the saw.
>>>>>>>>>> If wired for 120 V I would say yes, if wire for 240 V probably not.
>>>>>>>>>>
>>>>>>>>> 20 amps is 20 amps. Don't matter whether you're running 120 or 240.
>>>>>>>> Yes but a 240 V circuit has two 20 amp leads, a motor drawing 20 amps,
>>>>>>>> 10 per leg.
>>>>>>>>
>>>>>>>> Mark
>>>>>>> Current (when there is a load) is the same at any place in the circuit, regardless of being 120 or 240.
>>>>>> However a more that needs 20 amps at 110 volts only needs 10 at 220.
>>>>> That's because it gets 10 amps on Each of Two legs at the same time (I
>>>>> think "legs" is the right word, I could be wrong).
>>>> Even though this is not DC...Ohm's Law says your theory is wrong. I=E/R, if you double the voltage you halve the current. Also, wattage would prove that out. The same motor wired 240, would draw
>>> I get it. I'm also gently reminded/informed that a 240V circuit is Not
>>> the equivalent of two 120v circuits.
>> It is, really, except that the two circuits are out of phase, so they
>> add (if they were in-phase, they'd subtract).
>
>That comment makes me wonder whether you really understand--as well as
>Bob Villa has explained it.

Wonder about what? What I said is correct, with a possible niggle
about "circuits" (without the neutral there is only one).

Frankly, I didn't understand "( ?~ ?? ?°)". ;-)

BB

Bill

in reply to FrozenNorth on 08/06/2016 3:19 PM

09/06/2016 11:40 PM

krw wrote:
> On Thu, 9 Jun 2016 22:35:29 -0400, Bill <[email protected]>
> wrote:
>
>> krw wrote:
>>> On Thu, 9 Jun 2016 17:23:47 -0400, Bill <[email protected]>
>>> wrote:
>>>
>>>> Bob Villa wrote:
>>>>> On Thursday, June 9, 2016 at 1:45:41 AM UTC-5, Bill wrote:
>>>>>> J. Clarke wrote:
>>>>>>> In article <[email protected]>,
>>>>>>> [email protected] says...
>>>>>>>> On Wednesday, June 8, 2016 at 8:55:19 PM UTC-5, Markem wrote:
>>>>>>>>> On Wed, 8 Jun 2016 21:30:09 -0400, Mike Marlow
>>>>>>>>> <[email protected]> wrote:
>>>>>>>>>
>>>>>>>>>> Markem wrote:
>>>>>>>>>>> On Wed, 8 Jun 2016 15:19:50 -0400, FrozenNorth
>>>>>>>>>>> <[email protected]> wrote:
>>>>>>>>>>>
>>>>>>>>>>>> On 2016-06-08 3:07 PM, Bill wrote:
>>>>>>>>>>>>> Bill wrote:
>>>>>>>>>>>>>> In the owner's manual for my (new to me) Delta TS (36-841), it says:
>>>>>>>>>>>>>>
>>>>>>>>>>>>>> "This circuit should not be less than #12 wire and should be protected
>>>>>>>>>>>>>> with a 20 Amp time lag fuse."
>>>>>>>>>>>>>>
>>>>>>>>>>>>>> Not being aware of this detail until now, I was just going to use a
>>>>>>>>>>>>>> regular 20-Amp circuit-breaker (I ran #12 wire).
>>>>>>>>>>>>> Correction, I ran #10 wire, for this.
>>>>>>>>>>>>>
>>>>>>>>>>>>>
>>>>>>>>>>>>>> Please advise. Thank you!
>>>>>>>>>>>>>>
>>>>>>>>>>>>>> Bill
>>>>>>>>>>>> Prepare for a few breaker pops, hope the fuse panel is close to the saw.
>>>>>>>>>>> If wired for 120 V I would say yes, if wire for 240 V probably not.
>>>>>>>>>>>
>>>>>>>>>> 20 amps is 20 amps. Don't matter whether you're running 120 or 240.
>>>>>>>>> Yes but a 240 V circuit has two 20 amp leads, a motor drawing 20 amps,
>>>>>>>>> 10 per leg.
>>>>>>>>>
>>>>>>>>> Mark
>>>>>>>> Current (when there is a load) is the same at any place in the circuit, regardless of being 120 or 240.
>>>>>>> However a more that needs 20 amps at 110 volts only needs 10 at 220.
>>>>>> That's because it gets 10 amps on Each of Two legs at the same time (I
>>>>>> think "legs" is the right word, I could be wrong).
>>>>> Even though this is not DC...Ohm's Law says your theory is wrong. I=E/R, if you double the voltage you halve the current. Also, wattage would prove that out. The same motor wired 240, would draw
>>>> I get it. I'm also gently reminded/informed that a 240V circuit is Not
>>>> the equivalent of two 120v circuits.
>>> It is, really, except that the two circuits are out of phase, so they
>>> add (if they were in-phase, they'd subtract).
>> That comment makes me wonder whether you really understand--as well as
>> Bob Villa has explained it.
> Wonder about what?

The flow of electricity in the 240v versus 120v circuits (feel free to
show me that I'm wrong, and I'll be the first to admit it).



> What I said is correct, with a possible niggle
> about "circuits" (without the neutral there is only one).
>
> Frankly, I didn't understand "( ?~ ?? ?°)". ;-)
>

BB

Bill

in reply to Bill on 08/06/2016 3:05 PM

08/06/2016 3:18 PM

Bill wrote:
> Bill wrote:
>> In the owner's manual for my (new to me) Delta TS (36-841), it says:
>>
>> "This circuit should not be less than #12 wire and should be
>> protected with a 20 Amp time lag fuse."
>>
>> Not being aware of this detail until now, I was just going to use a
>> regular 20-Amp circuit-breaker (I ran #12 wire).
>
> Correction, I ran #10 wire, for this.
Also when I say "regular", I do mean 240v (2-pole).

Thanks!
Bill


>
>
>> Please advise. Thank you!
>>
>> Bill
>

BB

Bill

in reply to Bill on 08/06/2016 3:05 PM

08/06/2016 4:06 PM


>> Bill wrote:
>>> In the owner's manual for my (new to me) Delta TS (36-841), it says:
>>>
>>> "This circuit should not be less than #12 wire and should be
>>> protected with a 20 Amp time lag fuse."
>>>
>>> Not being aware of this detail until now, I was just going to use a
>>> regular 20-Amp circuit-breaker (I ran #12 wire).
>>
>> Correction, I ran #10 wire, for this.
> Also when I say "regular", I do mean 240v (2-pole).
>
> Thanks!
> Bill
>
> Please advise. Thank you!

In trying to answer my question, I learned that
"all circuit breakers are "time delay" by nature of their design."

So, I guess we'll see what happens...

Progress in the shop is continuing after a delay or two in recent years
caused by major events.

Bill

dn

dpb

in reply to Bill on 08/06/2016 3:05 PM

08/06/2016 3:14 PM

On 06/08/2016 2:19 PM, FrozenNorth wrote:
> On 2016-06-08 3:07 PM, Bill wrote:
>> Bill wrote:
>>> In the owner's manual for my (new to me) Delta TS (36-841), it says:
>>>
>>> "This circuit should not be less than #12 wire and should be protected
>>> with a 20 Amp time lag fuse."
>>>
>>> Not being aware of this detail until now, I was just going to use a
>>> regular 20-Amp circuit-breaker (I ran #12 wire).
>>
>> Correction, I ran #10 wire, for this.
>>
>>
>>> Please advise. Thank you!
>>>
>>> Bill
>>
> Prepare for a few breaker pops, hope the fuse panel is close to the saw.

Nope, he'll be fine (as he discovered in further research and posted) as
circuit breaker as opposed to fast-acting fuse has enough inherent lag
time for the motor...

--


Mm

-MIKE-

in reply to Bill on 08/06/2016 3:05 PM

08/06/2016 3:59 PM

On 6/8/16 2:05 PM, Bill wrote:
> In the owner's manual for my (new to me) Delta TS (36-841), it says:
>
> "This circuit should not be less than #12 wire and should be protected
> with a 20 Amp time lag fuse."
>
> Not being aware of this detail until now, I was just going to use a
> regular 20-Amp circuit-breaker (I ran #12 wire). Please advise. Thank you!
>
> Bill

As others are pointing out, you'll be fine.
Old fuses would blow with the initial spike of current when saw motor
kicked on.
A modern circuit breaker needs to heat up to trip (except in the case of
a short) so it can't get hot enough to trip from the very short current
spike of the motor's start-up.

At least that's my layman's explanation of it. :-)


--

-MIKE-

"Playing is not something I do at night, it's my function in life"
--Elvin Jones (1927-2004)
--
http://mikedrums.com
[email protected]
---remove "DOT" ^^^^ to reply

dn

dpb

in reply to Bill on 08/06/2016 3:05 PM

08/06/2016 4:43 PM

On 06/08/2016 3:59 PM, -MIKE- wrote:
...

> Old fuses would blow with the initial spike of current when saw motor
> kicked on.

"Fast-acting" ones, yes, "slo-blo" (specifically designed for motor
loads and the like with an initial short-lived high-current transient)
wouldn't.

> A modern circuit breaker needs to heat up to trip (except in the case of
> a short) so it can't get hot enough to trip from the very short current
> spike of the motor's start-up.
...

The fuse had to heat up, too (in fact, it had to actually melt) but the
idea is correct; they are designed to handle motor loads inherently to
be general-purpose; it would be a real pain to have to have separate
breakers for the application.

The time for a dead short to heat up and trip will be quite a lot
shorter than that for the motor start; while a motor start is a
(relatively) high current (say 3X or so of full load), that of a dead
short is I=V/(R-->zero) --> Infinite.

--

MM

Mike Marlow

in reply to Bill on 08/06/2016 3:05 PM

08/06/2016 5:59 PM

FrozenNorth wrote:
> On 2016-06-08 3:07 PM, Bill wrote:
>> Bill wrote:
>>> In the owner's manual for my (new to me) Delta TS (36-841), it says:
>>>
>>> "This circuit should not be less than #12 wire and should be protected
>>> with a 20 Amp time lag fuse."
>>>
>>> Not being aware of this detail until now, I was just going to use a
>>> regular 20-Amp circuit-breaker (I ran #12 wire).
>>
>> Correction, I ran #10 wire, for this.
>>
>>
>>> Please advise. Thank you!
>>>
>>> Bill
>>
> Prepare for a few breaker pops, hope the fuse panel is close to the saw.
>

Don't know why you'd say that. He's well within the current loads with
#12 wire and an 20A breaker.

--
-Mike-
[email protected]

MM

Mike Marlow

in reply to Bill on 08/06/2016 3:05 PM

08/06/2016 6:38 PM

dpb wrote:
> On 06/08/2016 3:59 PM, -MIKE- wrote:
> ...
>
>> Old fuses would blow with the initial spike of current when saw motor
>> kicked on.
>
> "Fast-acting" ones, yes, "slo-blo" (specifically designed for motor
> loads and the like with an initial short-lived high-current transient)
> wouldn't.
>
>> A modern circuit breaker needs to heat up to trip (except in the case of
>> a short) so it can't get hot enough to trip from the very short current
>> spike of the motor's start-up.
> ...
>
> The fuse had to heat up, too (in fact, it had to actually melt) but the
> idea is correct; they are designed to handle motor loads inherently to
> be general-purpose; it would be a real pain to have to have separate
> breakers for the application.
>
> The time for a dead short to heat up and trip will be quite a lot
> shorter than that for the motor start; while a motor start is a
> (relatively) high current (say 3X or so of full load), that of a dead
> short is I=V/(R-->zero) --> Infinite.
>

So... you basically agreed with the previous poster...


--
-Mike-
[email protected]

dn

dpb

in reply to Bill on 08/06/2016 3:05 PM

08/06/2016 5:46 PM

On 06/08/2016 5:38 PM, Mike Marlow wrote:
> dpb wrote:
>> On 06/08/2016 3:59 PM, -MIKE- wrote:
>> ...
>>
>>> Old fuses would blow with the initial spike of current when saw motor
>>> kicked on.
>>
>> "Fast-acting" ones, yes, "slo-blo" (specifically designed for motor
>> loads and the like with an initial short-lived high-current transient)
>> wouldn't.
>>
>>> A modern circuit breaker needs to heat up to trip (except in the case of
>>> a short) so it can't get hot enough to trip from the very short current
>>> spike of the motor's start-up.
>> ...
>>
>> The fuse had to heat up, too (in fact, it had to actually melt) but the
>> idea is correct; they are designed to handle motor loads inherently to
>> be general-purpose; it would be a real pain to have to have separate
>> breakers for the application.
>>
>> The time for a dead short to heat up and trip will be quite a lot
>> shorter than that for the motor start; while a motor start is a
>> (relatively) high current (say 3X or so of full load), that of a dead
>> short is I=V/(R-->zero) --> Infinite.
>>
>
> So... you basically agreed with the previous poster...

Well, yes, I said that in the very beginning that his general ideas
were/are correct but added some amplification as to "why" and "what"
actually is going on.

Was that needing comment for some reason?

--

MM

Mike Marlow

in reply to Bill on 08/06/2016 3:05 PM

08/06/2016 6:49 PM

dpb wrote:
> On 06/08/2016 5:38 PM, Mike Marlow wrote:
>> dpb wrote:
>>> On 06/08/2016 3:59 PM, -MIKE- wrote:
>>> ...
>>>
>>>> Old fuses would blow with the initial spike of current when saw motor
>>>> kicked on.
>>>
>>> "Fast-acting" ones, yes, "slo-blo" (specifically designed for motor
>>> loads and the like with an initial short-lived high-current transient)
>>> wouldn't.
>>>
>>>> A modern circuit breaker needs to heat up to trip (except in the
>>>> case of
>>>> a short) so it can't get hot enough to trip from the very short current
>>>> spike of the motor's start-up.
>>> ...
>>>
>>> The fuse had to heat up, too (in fact, it had to actually melt) but the
>>> idea is correct; they are designed to handle motor loads inherently to
>>> be general-purpose; it would be a real pain to have to have separate
>>> breakers for the application.
>>>
>>> The time for a dead short to heat up and trip will be quite a lot
>>> shorter than that for the motor start; while a motor start is a
>>> (relatively) high current (say 3X or so of full load), that of a dead
>>> short is I=V/(R-->zero) --> Infinite.
>>>
>>
>> So... you basically agreed with the previous poster...
>
> Well, yes, I said that in the very beginning that his general ideas
> were/are correct but added some amplification as to "why" and "what"
> actually is going on.
>
> Was that needing comment for some reason?
>

Maybe my fault for having missed that up front. Sorry.



--
-Mike-
[email protected]

MM

Mike Marlow

in reply to Bill on 08/06/2016 3:05 PM

08/06/2016 9:30 PM

Markem wrote:
> On Wed, 8 Jun 2016 15:19:50 -0400, FrozenNorth
> <[email protected]> wrote:
>
>> On 2016-06-08 3:07 PM, Bill wrote:
>>> Bill wrote:
>>>> In the owner's manual for my (new to me) Delta TS (36-841), it says:
>>>>
>>>> "This circuit should not be less than #12 wire and should be protected
>>>> with a 20 Amp time lag fuse."
>>>>
>>>> Not being aware of this detail until now, I was just going to use a
>>>> regular 20-Amp circuit-breaker (I ran #12 wire).
>>>
>>> Correction, I ran #10 wire, for this.
>>>
>>>
>>>> Please advise. Thank you!
>>>>
>>>> Bill
>>>
>> Prepare for a few breaker pops, hope the fuse panel is close to the saw.
>
> If wired for 120 V I would say yes, if wire for 240 V probably not.
>

20 amps is 20 amps. Don't matter whether you're running 120 or 240.



--
-Mike-
[email protected]

BV

Bob Villa

in reply to Mike Marlow on 08/06/2016 9:30 PM

10/06/2016 7:27 AM

On Friday, June 10, 2016 at 9:11:36 AM UTC-5, Markem wrote:
> On Thu, 9 Jun 2016 23:40:47 -0400, Bill <[email protected]>
> wrote:
>=20
> >The flow of electricity in the 240v versus 120v circuits (feel free to=
=20
> >show me that I'm wrong, and I'll be the first to admit it).
>=20
> First off there is a single phase, a 240v circuit needs no neutral.
>=20
> The potential of the two legs is 180 degrees different to cause that
> potential.
>=20
> A 120v circuit require a neutral return path.
>=20
> If you have two signals that are 180 degrees out of phase they cancel
> each other. That would be a two phase system and you only have one.

The "potential" is a voltage term. The 2 "hot" wires are in phase for 240 s=
ingle phase. If you took 2 120 Volt circuits from the same side of the pane=
l (in phase) black to black, white to white...you would have effectively, t=
he same circuit at 120 V. 240 out of phase? Not sure of the consequences of=
that!

Mm

Markem

in reply to Mike Marlow on 08/06/2016 9:30 PM

10/06/2016 9:11 AM

On Thu, 9 Jun 2016 23:40:47 -0400, Bill <[email protected]>
wrote:

>The flow of electricity in the 240v versus 120v circuits (feel free to
>show me that I'm wrong, and I'll be the first to admit it).

First off there is a single phase, a 240v circuit needs no neutral.

The potential of the two legs is 180 degrees different to cause that
potential.

A 120v circuit require a neutral return path.

If you have two signals that are 180 degrees out of phase they cancel
each other. That would be a two phase system and you only have one.

BB

Bill

in reply to Mike Marlow on 08/06/2016 9:30 PM

10/06/2016 1:40 PM

Bob Villa wrote:
> If you took 2 120 Volt circuits from the same side of the panel (in
> phase) black to black, white to white...you would have effectively,
> the same circuit at 120 V. 240 out of phase? Not sure of the
> consequences of that!

Don't they call that a "run" (of outlets, say)?

BB

Bill

in reply to Bill on 08/06/2016 3:05 PM

08/06/2016 9:58 PM

krw wrote:
> dpb <[email protected]> wrote:
>
>> -MIKE- wrote:
>>

The OP is satisfied. I just bought a outlet to match the saw's male
connector.

There's nothing like an electrical thread to create action around here.
Thank you for your willingness to help!

Bill

BB

Bill

in reply to Bill on 08/06/2016 3:05 PM

09/06/2016 2:44 AM

J. Clarke wrote:
> In article <[email protected]>,
> [email protected] says...
>> On Wednesday, June 8, 2016 at 8:55:19 PM UTC-5, Markem wrote:
>>> On Wed, 8 Jun 2016 21:30:09 -0400, Mike Marlow
>>> <[email protected]> wrote:
>>>
>>>> Markem wrote:
>>>>> On Wed, 8 Jun 2016 15:19:50 -0400, FrozenNorth
>>>>> <[email protected]> wrote:
>>>>>
>>>>>> On 2016-06-08 3:07 PM, Bill wrote:
>>>>>>> Bill wrote:
>>>>>>>> In the owner's manual for my (new to me) Delta TS (36-841), it says:
>>>>>>>>
>>>>>>>> "This circuit should not be less than #12 wire and should be protected
>>>>>>>> with a 20 Amp time lag fuse."
>>>>>>>>
>>>>>>>> Not being aware of this detail until now, I was just going to use a
>>>>>>>> regular 20-Amp circuit-breaker (I ran #12 wire).
>>>>>>> Correction, I ran #10 wire, for this.
>>>>>>>
>>>>>>>
>>>>>>>> Please advise. Thank you!
>>>>>>>>
>>>>>>>> Bill
>>>>>> Prepare for a few breaker pops, hope the fuse panel is close to the saw.
>>>>> If wired for 120 V I would say yes, if wire for 240 V probably not.
>>>>>
>>>> 20 amps is 20 amps. Don't matter whether you're running 120 or 240.
>>> Yes but a 240 V circuit has two 20 amp leads, a motor drawing 20 amps,
>>> 10 per leg.
>>>
>>> Mark
>> Current (when there is a load) is the same at any place in the circuit, regardless of being 120 or 240.
> However a more that needs 20 amps at 110 volts only needs 10 at 220.
That's because it gets 10 amps on Each of Two legs at the same time (I
think "legs" is the right word, I could be wrong).

BB

Bill

in reply to Bill on 08/06/2016 3:05 PM

09/06/2016 2:59 PM

Swingman wrote:
>
> Have at it, you're set to make sawdust ... no further need for bits
> and bytes.

Thank you! But I rather enjoy the bits and bytes that connect me with
other folks, such as yourself!

Bill

BB

Bill

in reply to Bill on 08/06/2016 3:05 PM

09/06/2016 5:23 PM

Bob Villa wrote:
> On Thursday, June 9, 2016 at 1:45:41 AM UTC-5, Bill wrote:
>> J. Clarke wrote:
>>> In article <[email protected]>,
>>> [email protected] says...
>>>> On Wednesday, June 8, 2016 at 8:55:19 PM UTC-5, Markem wrote:
>>>>> On Wed, 8 Jun 2016 21:30:09 -0400, Mike Marlow
>>>>> <[email protected]> wrote:
>>>>>
>>>>>> Markem wrote:
>>>>>>> On Wed, 8 Jun 2016 15:19:50 -0400, FrozenNorth
>>>>>>> <[email protected]> wrote:
>>>>>>>
>>>>>>>> On 2016-06-08 3:07 PM, Bill wrote:
>>>>>>>>> Bill wrote:
>>>>>>>>>> In the owner's manual for my (new to me) Delta TS (36-841), it says:
>>>>>>>>>>
>>>>>>>>>> "This circuit should not be less than #12 wire and should be protected
>>>>>>>>>> with a 20 Amp time lag fuse."
>>>>>>>>>>
>>>>>>>>>> Not being aware of this detail until now, I was just going to use a
>>>>>>>>>> regular 20-Amp circuit-breaker (I ran #12 wire).
>>>>>>>>> Correction, I ran #10 wire, for this.
>>>>>>>>>
>>>>>>>>>
>>>>>>>>>> Please advise. Thank you!
>>>>>>>>>>
>>>>>>>>>> Bill
>>>>>>>> Prepare for a few breaker pops, hope the fuse panel is close to the saw.
>>>>>>> If wired for 120 V I would say yes, if wire for 240 V probably not.
>>>>>>>
>>>>>> 20 amps is 20 amps. Don't matter whether you're running 120 or 240.
>>>>> Yes but a 240 V circuit has two 20 amp leads, a motor drawing 20 amps,
>>>>> 10 per leg.
>>>>>
>>>>> Mark
>>>> Current (when there is a load) is the same at any place in the circuit, regardless of being 120 or 240.
>>> However a more that needs 20 amps at 110 volts only needs 10 at 220.
>> That's because it gets 10 amps on Each of Two legs at the same time (I
>> think "legs" is the right word, I could be wrong).
> Even though this is not DC...Ohm's Law says your theory is wrong. I=E/R, if you double the voltage you halve the current. Also, wattage would prove that out. The same motor wired 240, would draw

I get it. I'm also gently reminded/informed that a 240V circuit is Not
the equivalent of two 120v circuits.

Thanks,
Bill


> half what it did on 120. On single phase, the neutral (white or ground) is the center-tap of the power transformer. That's why it's half the voltage.

BB

Bill

in reply to Bill on 08/06/2016 3:05 PM

09/06/2016 5:57 PM

Leon wrote:
> On 6/9/2016 4:23 PM, Bill wrote:
>> Bob Villa wrote:
>>> Even though this is not DC...Ohm's Law says your theory is wrong.
>>> I=E/R, if you double the voltage you halve the current. Also, wattage
>>> would prove that out. The same motor wired 240, would draw
>>
>> I get it. I'm also gently reminded/informed that a 240V circuit is Not
>> the equivalent of two 120v circuits.
>
>
> But you do realize that the 240 in your home is made up of 2 out of
> phase 120 circuits...
>

Yes, that's most-surely what led to my confusion about the way a 240v
circuit works...
So, a 240v circuit apparently doesn't have a direction....or rather, it
has 2 directions at the same time, from one leg to another, and vice-versa.

Bill

BB

Bill

in reply to Bill on 08/06/2016 3:05 PM

09/06/2016 8:55 PM

Bob Villa wrote:
> On Thursday, June 9, 2016 at 4:58:37 PM UTC-5, Bill wrote:
>> Leon wrote:
>>> On 6/9/2016 4:23 PM, Bill wrote:
>>>> Bob Villa wrote:
>>>>> Even though this is not DC...Ohm's Law says your theory is wrong.
>>>>> I=E/R, if you double the voltage you halve the current. Also, wattage
>>>>> would prove that out. The same motor wired 240, would draw
>>>> I get it. I'm also gently reminded/informed that a 240V circuit is Not
>>>> the equivalent of two 120v circuits.
>>>
>>> But you do realize that the 240 in your home is made up of 2 out of
>>> phase 120 circuits...
>>>
>> Yes, that's most-surely what led to my confusion about the way a 240v
>> circuit works...
>> So, a 240v circuit apparently doesn't have a direction....or rather, it
>> has 2 directions at the same time, from one leg to another, and vice-versa.
>>
>> Bill
> ...half of your 120 volt circuits would be out of phase with the other half. And there are 120 direction changes (60 cycles) in one second.

I get it! Thanks! Am I the only one here who didn't know that? :)

Bill

BB

Bill

in reply to Bill on 08/06/2016 3:05 PM

09/06/2016 10:35 PM

krw wrote:
> On Thu, 9 Jun 2016 17:23:47 -0400, Bill <[email protected]>
> wrote:
>
>> Bob Villa wrote:
>>> On Thursday, June 9, 2016 at 1:45:41 AM UTC-5, Bill wrote:
>>>> J. Clarke wrote:
>>>>> In article <[email protected]>,
>>>>> [email protected] says...
>>>>>> On Wednesday, June 8, 2016 at 8:55:19 PM UTC-5, Markem wrote:
>>>>>>> On Wed, 8 Jun 2016 21:30:09 -0400, Mike Marlow
>>>>>>> <[email protected]> wrote:
>>>>>>>
>>>>>>>> Markem wrote:
>>>>>>>>> On Wed, 8 Jun 2016 15:19:50 -0400, FrozenNorth
>>>>>>>>> <[email protected]> wrote:
>>>>>>>>>
>>>>>>>>>> On 2016-06-08 3:07 PM, Bill wrote:
>>>>>>>>>>> Bill wrote:
>>>>>>>>>>>> In the owner's manual for my (new to me) Delta TS (36-841), it says:
>>>>>>>>>>>>
>>>>>>>>>>>> "This circuit should not be less than #12 wire and should be protected
>>>>>>>>>>>> with a 20 Amp time lag fuse."
>>>>>>>>>>>>
>>>>>>>>>>>> Not being aware of this detail until now, I was just going to use a
>>>>>>>>>>>> regular 20-Amp circuit-breaker (I ran #12 wire).
>>>>>>>>>>> Correction, I ran #10 wire, for this.
>>>>>>>>>>>
>>>>>>>>>>>
>>>>>>>>>>>> Please advise. Thank you!
>>>>>>>>>>>>
>>>>>>>>>>>> Bill
>>>>>>>>>> Prepare for a few breaker pops, hope the fuse panel is close to the saw.
>>>>>>>>> If wired for 120 V I would say yes, if wire for 240 V probably not.
>>>>>>>>>
>>>>>>>> 20 amps is 20 amps. Don't matter whether you're running 120 or 240.
>>>>>>> Yes but a 240 V circuit has two 20 amp leads, a motor drawing 20 amps,
>>>>>>> 10 per leg.
>>>>>>>
>>>>>>> Mark
>>>>>> Current (when there is a load) is the same at any place in the circuit, regardless of being 120 or 240.
>>>>> However a more that needs 20 amps at 110 volts only needs 10 at 220.
>>>> That's because it gets 10 amps on Each of Two legs at the same time (I
>>>> think "legs" is the right word, I could be wrong).
>>> Even though this is not DC...Ohm's Law says your theory is wrong. I=E/R, if you double the voltage you halve the current. Also, wattage would prove that out. The same motor wired 240, would draw
>> I get it. I'm also gently reminded/informed that a 240V circuit is Not
>> the equivalent of two 120v circuits.
> It is, really, except that the two circuits are out of phase, so they
> add (if they were in-phase, they'd subtract).

That comment makes me wonder whether you really understand--as well as
Bob Villa has explained it.


>
>
>> Thanks,
>> Bill
>>
>>
>>> half what it did on 120. On single phase, the neutral (white or ground) is the center-tap of the power transformer. That's why it's half the voltage.
>
> Yes, on the pole, and the neutral is brought into the panel. However,
> there is no neutral in this (240V) circuit. It's not needed because
> the saw doesn't use 120V (if wired for 240V).
>
>

kk

krw

in reply to Bill on 08/06/2016 3:05 PM

08/06/2016 9:48 PM

On Wed, 8 Jun 2016 21:30:09 -0400, Mike Marlow
<[email protected]> wrote:

>Markem wrote:
>> On Wed, 8 Jun 2016 15:19:50 -0400, FrozenNorth
>> <[email protected]> wrote:
>>
>>> On 2016-06-08 3:07 PM, Bill wrote:
>>>> Bill wrote:
>>>>> In the owner's manual for my (new to me) Delta TS (36-841), it says:
>>>>>
>>>>> "This circuit should not be less than #12 wire and should be protected
>>>>> with a 20 Amp time lag fuse."
>>>>>
>>>>> Not being aware of this detail until now, I was just going to use a
>>>>> regular 20-Amp circuit-breaker (I ran #12 wire).
>>>>
>>>> Correction, I ran #10 wire, for this.
>>>>
>>>>
>>>>> Please advise. Thank you!
>>>>>
>>>>> Bill
>>>>
>>> Prepare for a few breaker pops, hope the fuse panel is close to the saw.
>>
>> If wired for 120 V I would say yes, if wire for 240 V probably not.
>>
>
>20 amps is 20 amps. Don't matter whether you're running 120 or 240.

Not true. The motor will draw half the current at 240V, as it would
wired for 120V.

kk

krw

in reply to Bill on 08/06/2016 3:05 PM

11/06/2016 11:28 AM

On Sat, 11 Jun 2016 05:54:24 -0400, "J. Clarke"
<[email protected]> wrote:

>In article <[email protected]>,
>[email protected] says...
>>
>> Bill <[email protected]> wrote in news:[email protected]:
>>
>> > In the owner's manual for my (new to me) Delta TS (36-841), it says:
>> >
>> > "This circuit should not be less than #12 wire and should be protected
>> > with a 20 Amp time lag fuse."
>> >
>> > Not being aware of this detail until now, I was just going to use a
>> > regular 20-Amp circuit-breaker (I ran #12 wire). Please advise. Thank you!
>> >
>> 20 amp circuit breaker is fine.
>
>The breaker equivalent of a "slow-blow" fuse is called a "high
>magnetic" breaker. If your regular breaker is tripping on startup you
>might want to consider going that route. Personally when I run into tht
>though I generally just rewire the tool for 220 (if that's an option)
>and run a dedicated circuit. Most tools seem happier with 220 anyway.

Running large stationary tools at 240V is certainly recommended (I
think the OP has already gone that way) but there isn't a lot of
reason to run dedicated circuits in a home shop. Several tools can
share the circuit, since you aren't likely to use them simultaneously.
The exception, of course, is a DC.

kk

krw

in reply to Bill on 08/06/2016 3:05 PM

08/06/2016 8:15 PM

On Wed, 8 Jun 2016 15:05:14 -0400, Bill <[email protected]>
wrote:

>In the owner's manual for my (new to me) Delta TS (36-841), it says:
>
>"This circuit should not be less than #12 wire and should be protected
>with a 20 Amp time lag fuse."
>
>Not being aware of this detail until now, I was just going to use a
>regular 20-Amp circuit-breaker (I ran #12 wire). Please advise. Thank you!

You're good to go. Household circuit breakers are pretty much
equivalent to "slow blow" fuses.

kk

krw

in reply to Bill on 08/06/2016 3:05 PM

09/06/2016 10:12 PM

On Thu, 9 Jun 2016 05:42:47 -0700 (PDT), Sonny <[email protected]>
wrote:

>On Thursday, June 9, 2016 at 7:19:16 AM UTC-5, Swingman wrote:
>> On 6/8/2016 2:07 PM, Bill wrote:
>> > Bill wrote:
>> >> In the owner's manual for my (new to me) Delta TS (36-841), it says:
>> >>
>> >> "This circuit should not be less than #12 wire and should be protected
>> >> with a 20 Amp time lag fuse."
>> >>
>> >> Not being aware of this detail until now, I was just going to use a
>> >> regular 20-Amp circuit-breaker (I ran #12 wire).
>> >
>> > Correction, I ran #10 wire, for this.
>>
>> Have at it, you're set to make sawdust ... no further need for bits and
>> bytes.
>>
>
>.... Unless he's using Austrailian electricity or has a Canadian saw/sideways breaker box!?

Does the Australian electricity turn the other way?


You’ve reached the end of replies