I jut received my G0500. It is pre-wired for 220V and the 2HP motor
pulls 12A at that voltage.
Currently (no pun intended) the main tools in my shop are a 2 1/2 HP
Bandsaw and a 3HP table saw. I am a one-man shop and have no need for
the bandsaw and table saw to be running simultaneously. So, they both
run on a single 220V 20A 'dedicated' circuit. Neither tool manual
suggested a maximum CB amperage.
The Grizzly manual is very specific about running the Jointer on a (220)
15A circuit because "circuit breakers rated any higher are not adequate
to protect the circuit." Earlier in the same paragraph, though, they
talk about "...the following guidelines when choosing a circuit
breaker." So, guidelines or edicts?
I had planned on using the same 20A circuit for the jointer. If it
pulls 12A under normal conditions, placing it on a 15A circuit seems to
be hoping for the best. The internal wiring from the starter and switch
on the jointer are 14 gauge. It appears to me from other sources that
14 gauge can easily handle 20A. I don't know about the other
components, though.
I am reluctant to disreguard a manufacturer's guidance. I suppose I
will check with Grizzly support for their answer, but I am curious about
how the rec feels about this question.
Thanks for your help,
Charlie
I installed the starter switch box on this jointer a few days ago. It
includes a "Thermal Overload" device with a dial setting. The dial was
set to 15 at the factory.
This would appear to me - non-electrician - to protect the motor from
high temp from, for example, an over-current situation, which is the
subject of this thread.
If that is the case, the 15A CB on the circuit would be a back-up not
the sole protection.
I still have not received a reply from Grizzly tech support on this
question.
Charlie
[email protected] wrote:
> That's very interesting, considering I've got the G0586, which is
> supposed to be the replacement for the 500, and the spec says it pulls
> 12A at 220V and that it's a 2HP motor, and recommends a 20A fuse.
>
> http://images.grizzly.com/grizzlycom/specsheets/G0586_ds.pdf
Start-up surge on that motor is going to surpass 15A by quite a lot.
With a new breaker, it should be fine at 15A. But if you have an old
breaker, or a motor with a higher than usual starting surge, whoops!
Grizzly made this sort of a recommendation for a bit, wanting smaller
breakers than most other makers recommended, to protect the tool, or so
the manuals said. The breaker is not there to protect the tool, but to
protect the circuit, and the house/shop/garage from the results of an
electrical surge massive enough to melt cable insulation.
I'd go with 20A. The only 230 volt circuits I have in my shop are 30A
(well, that's not true: the furnace is 60A). Anyway, never a problem
running 12 amp tools on them.
I received the reply from Grizzly Technical Support on this question.
First, let me say that the delay was apparently my fault. They
attempted to email me over a week ago, but I did not receive the
message. This was apparently due to my SPAM controls. After I entered
their email address into my Address Book, I had no problems.
The reply simply said that I could use the Jointer on a 20A circuit.
No surprise to most of you who responded.
Thanks for your help,
Charlie
I run my G0500 on a 220v 20 amp circuit. I haven't let the smoke out of it
so far. If you have a short that would cause the breaker to go, it shouldn't
be a problem.
"Seawulf" <[email protected]> wrote in message
news:Q3vcf.18$7B.1@fed1read02...
>I jut received my G0500. It is pre-wired for 220V and the 2HP motor pulls
>12A at that voltage.
>
> Currently (no pun intended) the main tools in my shop are a 2 1/2 HP
> Bandsaw and a 3HP table saw. I am a one-man shop and have no need for the
> bandsaw and table saw to be running simultaneously. So, they both run on
> a single 220V 20A 'dedicated' circuit. Neither tool manual suggested a
> maximum CB amperage.
>
> The Grizzly manual is very specific about running the Jointer on a (220)
> 15A circuit because "circuit breakers rated any higher are not adequate to
> protect the circuit." Earlier in the same paragraph, though, they talk
> about "...the following guidelines when choosing a circuit breaker." So,
> guidelines or edicts?
>
> I had planned on using the same 20A circuit for the jointer. If it pulls
> 12A under normal conditions, placing it on a 15A circuit seems to be
> hoping for the best. The internal wiring from the starter and switch on
> the jointer are 14 gauge. It appears to me from other sources that 14
> gauge can easily handle 20A. I don't know about the other components,
> though.
>
> I am reluctant to disreguard a manufacturer's guidance. I suppose I will
> check with Grizzly support for their answer, but I am curious about how
> the rec feels about this question.
>
> Thanks for your help,
> Charlie
> I am reluctant to disreguard a manufacturer's guidance. I suppose I
> will check with Grizzly support for their answer, but I am curious about
> how the rec feels about this question.
>
My desk lamp has #18 wire, and it is plugged into a 20a circuit. By
Grizzley's reasoning, it should have a 7a breaker instead.
I suppose it is possible that they know something we don't; that defective
design or components cause the machine to draw too much current for a period
of time, and is resulting in damaged machines. Rather than fix it, they are
requiring you to prevent it will small breakers. Unlikely, but possible.
Personally I would use the 20a circuit.
BTW, my cottage's 23.5a water heater was hooked up with #12 for 20 years
without any problems; if that gives you any confidence. Still, I replaced
it with #10.
Seawulf wrote:
<snip>
> I am reluctant to disreguard a manufacturer's guidance. I suppose I
> will check with Grizzly support for their answer, but I am curious about
> how the rec feels about this question.
>
> Thanks for your help,
> Charlie
Circuit breaker are meant to protect the wires to the outlets. The 20
amp cuicuit will be fine for the jointer.
--
Jack Novak
Buffalo, NY - USA
[email protected]
(Remove -SPAM- to send email)
"LM" <[email protected]> wrote in message
news:[email protected]...
> Seawulf wrote:
>> Bet I can find a bottom feeding lawyer that would love someone
> telling you to plug your jointer into a 20 amp circuit. :)
>
I bet you could. Some lawyers are that stupid.
He'd loose.
Seawulf wrote:
> I jut received my G0500. It is pre-wired for 220V and the 2HP motor
> pulls 12A at that voltage.
>
> Currently (no pun intended) the main tools in my shop are a 2 1/2 HP
> Bandsaw and a 3HP table saw. I am a one-man shop and have no need for
> the bandsaw and table saw to be running simultaneously. So, they both
> run on a single 220V 20A 'dedicated' circuit. Neither tool manual
> suggested a maximum CB amperage.
>
> The Grizzly manual is very specific about running the Jointer on a (220)
> 15A circuit because "circuit breakers rated any higher are not adequate
> to protect the circuit." Earlier in the same paragraph, though, they
> talk about "...the following guidelines when choosing a circuit
> breaker." So, guidelines or edicts?
>
> I had planned on using the same 20A circuit for the jointer. If it
> pulls 12A under normal conditions, placing it on a 15A circuit seems to
> be hoping for the best. The internal wiring from the starter and switch
> on the jointer are 14 gauge. It appears to me from other sources that
> 14 gauge can easily handle 20A. I don't know about the other
> components, though.
>
> I am reluctant to disreguard a manufacturer's guidance. I suppose I
> will check with Grizzly support for their answer, but I am curious about
> how the rec feels about this question.
>
> Thanks for your help,
> Charlie
What is the gauge of the power cord on the jointer, 14 gauge ?
If something fails you could draw 19 + amps on that power cord.
Bet I can find a bottom feeding lawyer that would love someone
telling you to plug your jointer into a 20 amp circuit. :)
Guideline: A circuit should not normally draw more than 80% of
the rated amperage of the breaker. 15 amps x .8 = 12 amps.
Edict: 14 Gauge Wire max 15 Amps. Your on your own Seawulf. Hope
you can swim.
BTW I have a King 15" planer, identical to a Grizzly 15",
See thread titled "Twins" a few days ago.
2 HP, probably the same motor as yours.
Runs fine on a 15 amp. 240 V circuit.